Sewer Resolve logoSewer Resolve

Groundwater and Buoyancy Calculator

Hydrostatic uplift, resisting load and factor of safety against flotation.

Inputs

Results

Factor of safety against flotation

1.74

Required 1.10 · uplift 32.9 kN

Hydrostatic uplift32.9kN
Resisting force57.3kN
Structure self weight57.3kN
Additional resisting load0.0kN
Submerged height1.90m
Plan footprint area1.767m²
FS 1.10 requiredFS 1.74

Resistances include structure self weight and any additional load entered. Soil friction, side adhesion and anchors are excluded unless entered as an additional load.

Calculation details

Engineering equations

U = γ_w · A · h_w

R = self weight + additional resisting load

FS = R / U

Variables

U
Hydrostatic uplift force (kN)
γ_w
Unit weight of water, 9.81 kN/m³
A
Plan footprint area of the structure (m²)
h_w
Submerged height from the structure base to groundwater level (m)
R
Total resisting force (kN)
FS
Factor of safety against flotation

Assumptions

  • Hydrostatic uplift acts over the full plan footprint of the structure.
  • Submerged height is measured from the structure base to the groundwater level; groundwater above the base only.
  • Resistance is structure self weight plus any additional resisting load entered.
  • Soil friction, side adhesion and anchors are excluded unless entered as an additional load.
  • Groundwater is assumed at rest with a horizontal water table.

Worked example

Maintenance hole, D_i = 1200 mm, wall 150 mm, ground level 25.00 m, base 21.60 m, groundwater 23.50 m, concrete 24 kN/m³

A = 1.77 m², h_w = 1.90 m, U = 9.81 × 1.77 × 1.90 = 32.9 kN

Self weight = 2.39 m³ × 24 = 57.3 kN

FS = 57.3 / 32.9 = 1.74

Results are preliminary engineering estimates based on the stated assumptions. Confirm inputs, assumptions and requirements against the applicable standards and authority requirements before use in design or construction.

Sewer Resolve logoSewer Resolve v0.1 Beta